Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)

Class II - Moderate

What Should You Do?

  1. Check if you have this product:
    (About 1,000)
  2. Do not eat it: Even if it looks and smells fine, do not consume this product.
  3. Throw it away or return it: You can return the product to the store for a full refund.
  4. Report problems: Report any issues to the FDA's Safety Reporting Portal.

Recall Details

Company:
Unknown Manufacturer
Reason for Recall:
When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
Classification:
Class II - Moderate

Products that might cause a temporary health problem, or pose a slight threat of a serious nature.

Status:
ongoing
Hazard:
When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
Remedy:
Consumers should immediately contact the distributor to obtain the free repair, a firmware upgrade.

Product Images

Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)

Product Information

Full Description:

This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.

Product Codes/Lot Numbers:

(About 1,000)

Official Source

Always verify recall information with the official CPSC source:

View on CPSC.gov

CPSC Recall Number: 16134

Related Recalls

AMP MP2 Smart Fitness Machine

Unknown Manufacturer

Class I - Dangerous

The arm on the MP2 model of the fitness machine does not lock properly, which can allow the arm to swing unexpectedly, posing a risk of laceration or serious injury.

Dec 18, 2025 Furniture Nationwide View Details →
Class I - Dangerous

The power strips do not contain supplementary overcurrent protection, which creates a risk of fire if the power strips are overloaded. The resulting fire can cause serious injury or death from smoke inhalation and burns.

Dec 18, 2025 Electronics Nationwide View Details →