Recall Details
- Company:
- Bosch Security Systems Inc., of Fairport, N.Y.
- Reason for Recall:
- The notification appliance circuit module can cause the panels to fail to activate an audible or visual alarm in the event of a fire.
- Classification:
- Class I - Dangerous
Dangerous or defective products that predictably could cause serious health problems or death.
- Status:
- ongoing
- Hazard:
- The notification appliance circuit module can cause the panels to fail to activate an audible or visual alarm in the event of a fire.
- Remedy:
- Consumers who have a recalled GV4 control panel with a D192G NAC module should contact Bosch or their certified professional installer for a free repair. Bosch has contacted their distributors and installers and sent installers a service bulletin telling them how to correct the problem.
Product Images

Product Information
Full Description:
The recall involves G-series Fire Alarm Control Panels that are professionally installed and have model numbers that end in GV4 and use D192G Notification Appliance Circuit (NAC) modules. The NAC module monitors the circuit connections and signals when alarms are not operational. The Bosch name, logo and model number D9412GV4, D7412GV4 or D7212GV4 are on the board of recalled GV4 fire alarm control panels. The control panels and modules are used in residences and commercial facilities and can be mounted inside a variety of enclosures with a minimum size of 16 inches x 16 inches x 3.5 inches, which may or may not be labeled with the Bosch name or logo.
Product Codes/Lot Numbers:
(About 2,000)
Official Source
Always verify recall information with the official CPSC source:
View on CPSC.govCPSC Recall Number: 14711
Related Recalls
Fire Alarm Control Panel
Bosch Security Systems, Inc., of Fairport, N.Y.
On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken.