Bosch GV4 Fire Alarm Control Panels

Class I - Dangerous

What Should You Do?

  1. Check if you have this product:
    (About 2,000)
  2. Do not eat it: Even if it looks and smells fine, do not consume this product.
  3. Throw it away or return it: You can return the product to the store for a full refund.
  4. Seek medical attention if needed: If you've consumed this product and feel unwell, contact your doctor immediately.
  5. Report problems: Report any issues to the FDA's Safety Reporting Portal.

⚠️ Emergency: If you experience severe symptoms after consuming this product, call 911 or Poison Control at 1-800-222-1222.

Recall Details

Company:
Bosch Security Systems Inc., of Fairport, N.Y.
Reason for Recall:
The notification appliance circuit module can cause the panels to fail to activate an audible or visual alarm in the event of a fire.
Classification:
Class I - Dangerous

Dangerous or defective products that predictably could cause serious health problems or death.

Status:
ongoing
Hazard:
The notification appliance circuit module can cause the panels to fail to activate an audible or visual alarm in the event of a fire.
Remedy:
Consumers who have a recalled GV4 control panel with a D192G NAC module should contact Bosch or their certified professional installer for a free repair. Bosch has contacted their distributors and installers and sent installers a service bulletin telling them how to correct the problem.

Product Images

Bosch GV4 Fire Alarm Control PanelsBosch GV4 Fire Alarm Control Panels

Product Information

Full Description:

The recall involves G-series Fire Alarm Control Panels that are professionally installed and have model numbers that end in GV4 and use D192G Notification Appliance Circuit (NAC) modules. The NAC module monitors the circuit connections and signals when alarms are not operational. The Bosch name, logo and model number D9412GV4, D7412GV4 or D7212GV4 are on the board of recalled GV4 fire alarm control panels. The control panels and modules are used in residences and commercial facilities and can be mounted inside a variety of enclosures with a minimum size of 16 inches x 16 inches x 3.5 inches, which may or may not be labeled with the Bosch name or logo.

Product Codes/Lot Numbers:

(About 2,000)

Official Source

Always verify recall information with the official CPSC source:

View on CPSC.gov

CPSC Recall Number: 14711

Related Recalls

Fire Alarm Control Panel

Bosch Security Systems, Inc., of Fairport, N.Y.

Class I - Dangerous

On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken.

Feb 15, 2012 Other Consumer Products Nationwide View Details →