Recall Details

Company:
Bosch Security Systems, Inc., of Fairport, N.Y.
Reason for Recall:
On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken.
Classification:
Class I - Dangerous

Dangerous or defective products that predictably could cause serious health problems or death.

Status:
ongoing
Hazard:
On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken.
Remedy:
All distributors and installers are being sent two technical bulletins. One provides instructions for how to implement a software change that will correct the verification feature. The second contains instructions for how to handle warnings from affected systems with 50 or more stations. Those who have not received the bulletins should contact Bosch.

Product Images

Fire Alarm Control Panel

Product Information

Full Description:

The Bosch-branded fire alarm panel is locking red wall box with dimensions 22.7" high by 14.5" wide by 4.3" deep. The status, date and time can be seen through a glass screen on the panel door. The word "BOSCH" is printed on the right corner of the panel and the model number "FPA-1000-UL" is printed on the bottom left below the glass screen. The alarm panels featured software versions 1.10, 1.11 and 1.12, which can be determined by installers. They were designed to be used in small to medium-sized facilities in both public and residential buildings.

Product Codes/Lot Numbers:

(About 330)

Official Source

Always verify recall information with the official CPSC source:

View on CPSC.gov

CPSC Recall Number: 12721

Related Recalls

Bosch GV4 Fire Alarm Control Panels

Bosch Security Systems Inc., of Fairport, N.Y.