PTEE and PTHE Series Packaged Terminal Air Conditioners (PTACs)

Class II - Moderate

What Should You Do?

  1. Check if you have this product:
    (About 10,580)
  2. Do not eat it: Even if it looks and smells fine, do not consume this product.
  3. Throw it away or return it: You can return the product to the store for a full refund.
  4. Report problems: Report any issues to the FDA's Safety Reporting Portal.

Recall Details

Company:
Qingdao Haier Air Conditioner, of Qingdao, China
Reason for Recall:
The heating element on these commercially installed units can become displaced and, if it contacts metal, could short circuit. If the electric heater on one of those units short-circuits, wiring problems on 265-volt models could allow the unit to remain energized while the unit's fan is turned off, causing it to overheat and smoke.
Classification:
Class II - Moderate

Products that might cause a temporary health problem, or pose a slight threat of a serious nature.

Status:
ongoing
Hazard:
The heating element on these commercially installed units can become displaced and, if it contacts metal, could short circuit. If the electric heater on one of those units short-circuits, wiring problems on 265-volt models could allow the unit to remain energized while the unit's fan is turned off, causing it to overheat and smoke.
Remedy:
The power connectors are being rewired or replaced, and the heaters will be visually inspected and replaced as necessary in the 265-volt models. Although there have been no incidents with the 208-volt and 230-volt models, Trane is still inspecting these units as a precaution. Trane has contacted the affected customers directly.

Product Images

PTEE and PTHE Series Packaged Terminal Air Conditioners (PTACs)

Product Information

Full Description:

The recall includes 208-, 230- and 265-volt models of the Trane PTEE and PTHE Series Packaged Terminal Air Conditioners (PTACs). They were manufactured from about March 2006 through July 2006. The date code is F06C through F06G, and is written on the unit's Manufacturer's Data Plate located behind the molded plastic cover above the power connection. The units have the following model numbers, also written on the Manufacturer's Data Plate: PTEE0701UAA PTEE1501UAA PTHE0902UAA PTEE0702UAA PTEE1502UAA PTHE1201UAA PTEE0901UAA PTHE0701UAA PTHE1202UAA PTEE0902UAA PTHE0702UAA PTHE1501UAA PTEE1201UAA PTHE0901UAA PTHE1502UAA PTEE1202UAA

Product Codes/Lot Numbers:

(About 10,580)

Official Source

Always verify recall information with the official CPSC source:

View on CPSC.gov

CPSC Recall Number: 07508