Cimberio Gas Ball Valve

Class II - Moderate

What Should You Do?

  1. Check if you have this product:
    (About 20,000 in inventory)
  2. Do not eat it: Even if it looks and smells fine, do not consume this product.
  3. Throw it away or return it: You can return the product to the store for a full refund.
  4. Report problems: Report any issues to the FDA's Safety Reporting Portal.

Recall Details

Company:
Cimberio S.p.A., of Via Torchio, Italy
Reason for Recall:
When one of these valves is closed, it could open up slightly. If the gas supply is on, gas will leak from the inlet port through the ball/seat and travel through the outlet port. If the valve is not connected to an appliance, and is not capped or plugged, as required by the National Fuel Gas Code Section 6.7.2.1, leaking gas will escape into the air. However, subsequent testing confirms that this potential for a gas leak is eliminated as gas flows through the valve. As a result, there is no risk with installed valves.
Classification:
Class II - Moderate

Products that might cause a temporary health problem, or pose a slight threat of a serious nature.

Status:
ongoing
Hazard:
When one of these valves is closed, it could open up slightly. If the gas supply is on, gas will leak from the inlet port through the ball/seat and travel through the outlet port. If the valve is not connected to an appliance, and is not capped or plugged, as required by the National Fuel Gas Code Section 6.7.2.1, leaking gas will escape into the air. However, subsequent testing confirms that this potential for a gas leak is eliminated as gas flows through the valve. As a result, there is no risk with installed valves.
Remedy:
Return any affected products that remain in inventory to Dormont.

Product Information

Full Description:

This inventory retrieval involves valves manufactured by Cimberio: ¾" FIP x 5/8" OD (15/16"-16 thread) Gas Ball Valve; ¾" FIP x ¾" FIP Gas Ball Valve; ¾" FIP x ¾" FIP Gas Ball Valve with Side Tap; ¾" FIP x ¾" FIP Gas Ball Valve with Square Head. All affected valves as described here have a red handle and have various markings on the valve body. See www.dormont.com for photographs of the affected valves.

Product Codes/Lot Numbers:

(About 20,000 in inventory)

Official Source

Always verify recall information with the official CPSC source:

View on CPSC.gov

CPSC Recall Number: 05569