Arc Fault Circuit Interrupters (AFCI)

Class I - Dangerous

What Should You Do?

  1. Check if you have this product:
    (About 700,000)
  2. Do not eat it: Even if it looks and smells fine, do not consume this product.
  3. Throw it away or return it: You can return the product to the store for a full refund.
  4. Seek medical attention if needed: If you've consumed this product and feel unwell, contact your doctor immediately.
  5. Report problems: Report any issues to the FDA's Safety Reporting Portal.

โš ๏ธ Emergency: If you experience severe symptoms after consuming this product, call 911 or Poison Control at 1-800-222-1222.

Recall Details

Company:
Schneider Electric North American Division, of Palatine, Ill.
Reason for Recall:
An AFCI is an electrical circuit protection device (circuit breaker) that detects electrical arcs from cracked, broken or damaged electrical insulation and shuts off power to the circuit before the arcing leads to a fire. An electronic component failure inside the AFCIs can cause the devices to not detect an electrical arc. Although the AFCIs will function as regular circuit breakers, they may not detect an arc fault, posing a safety risk to consumers.
Classification:
Class I - Dangerous

Dangerous or defective products that predictably could cause serious health problems or death.

Status:
ongoing
Hazard:
An AFCI is an electrical circuit protection device (circuit breaker) that detects electrical arcs from cracked, broken or damaged electrical insulation and shuts off power to the circuit before the arcing leads to a fire. An electronic component failure inside the AFCIs can cause the devices to not detect an electrical arc. Although the AFCIs will function as regular circuit breakers, they may not detect an arc fault, posing a safety risk to consumers.
Remedy:
Installed AFCIs will be replaced free of charge through electrical contractors. Consumers can return uninstalled AFCIs to the retailers or distributor from whom the unit was purchased for a free replacement unit.

Product Images

Arc Fault Circuit Interrupters (AFCI)Arc Fault Circuit Interrupters (AFCI)

Product Information

Full Description:

The recalled Square D QOยฎ and Homelineยฎ Arc Fault Interrupter circuit breakers are used with 15- and 20-amp branch circuits. They are required to be installed in bedroom circuits in accordance with the 2002 National Electrical Code. The recalled units were manufactured after March 1, 2004, and have a blue test button. The AFCI circuit breakers have one of the following date codes - CN, DN, EN, FN, GN, HN, or JN - stamped in red on the breaker label located just above the wiring terminal. The recalled units also have one of the following catalog numbers printed on a label on the front of the breaker: QO115AFI, QO115AFIC, QO120AFI, QO120AFIC, QOB115AFI, QOB120AFI, HOM115AFI, HOM115AFIC, HOM120AFI, HOM120AFIC, QO115VHAFI, QO120VHAFI, QOB115VHAFI, or QOB120VHAFI.

Product Codes/Lot Numbers:

(About 700,000)

Official Source

Always verify recall information with the official CPSC source:

View on CPSC.gov

CPSC Recall Number: 05035