Fire Alarm Control Panel
Class II - Moderate 🏠 Consumer Products
Recalled: October 30, 2003 Notifier, of Northford, Conn. Other Consumer Products
Nationwide
What Should You Do?
- Check if you have this product: (6,000)
- Do not eat it: Even if it looks and smells fine, do not consume this product.
- Throw it away or return it: You can return the product to the store for a full refund.
- Report problems: Report any issues to the FDA's Safety Reporting Portal.
Recall Details
- Company:
- Notifier, of Northford, Conn.
- Reason for Recall:
- The AEU can enter a "sleep" mode, where it does not communicate with the system. When this occurs, audible evacuation signals associated with the failed AEU will not operate and building occupants may not be warned of an emergency.
- Classification:
- Class II - Moderate
Products that might cause a temporary health problem, or pose a slight threat of a serious nature.
- Status:
- ongoing
- Hazard:
- The AEU can enter a "sleep" mode, where it does not communicate with the system. When this occurs, audible evacuation signals associated with the failed AEU will not operate and building occupants may not be warned of an emergency.
- Remedy:
- Notifier will provide an upgraded CPU firmware set for each AM2020 and AFP1010 panel, at no charge.
Product Images
Product Information
Full Description:
The fire alarm control panel includes the central processing unit (CPU-2020 and CPU-2) and Display Interface Assembly (DIA-2020 and DIA-2) components of Notifier model AM2020 and AFP1010 fire alarm control panels with date codes from 0100 to 2003 and firmware version 3.0 and 3.01. The date codes appear on the back outer edge of the PC boards.
Product Codes/Lot Numbers:
(6,000)
Official Source
Always verify recall information with the official CPSC source:
View on CPSC.govCPSC Recall Number: 04508
Related Recalls
Notifier Fire Alarm Control Panels
Notifier, of Northford, Conn.
Class I - Dangerous
The software in the fire alarm system could fail to process an alarm condition which could result in the system failing to respond in the event of a fire.