Package Terminal Air Conditioner/Heat Pump (PTAC)
Class I - DangerousWhat Should You Do?
- Check if you have this product: (About 875,000)
- Do not eat it: Even if it looks and smells fine, do not consume this product.
- Throw it away or return it: You can return the product to the store for a full refund.
- Seek medical attention if needed: If you've consumed this product and feel unwell, contact your doctor immediately.
- Report problems: Report any issues to the FDA's Safety Reporting Portal.
β οΈ Emergency: If you experience severe symptoms after consuming this product, call 911 or Poison Control at 1-800-222-1222.
Recall Details
- Company:
- Goodman Company, L.P., of Houston, Texas
- Reason for Recall:
- Fire hazard, resulting from this chain of events: filter becomes clogged due to lack of maintenance, severely restricting airflow and resulting in elevated internal temperature; this may cause two safety switches to stop working during the product's expected life; if the blower wheel then stops when the product is operated in the heating mode, a fire hazard can develop.
- Classification:
- Class I - Dangerous
Dangerous or defective products that predictably could cause serious health problems or death.
- Status:
- ongoing
- Hazard:
- Fire hazard, resulting from this chain of events: filter becomes clogged due to lack of maintenance, severely restricting airflow and resulting in elevated internal temperature; this may cause two safety switches to stop working during the product's expected life; if the blower wheel then stops when the product is operated in the heating mode, a fire hazard can develop.
- Remedy:
- Free thermal safety limit switch. Commercial and institutional owners will install the replacement switch themselves. Individual homeowners can get a free repair. Contact the Goodman Hotline to receive the free replacement thermal safety switch. Inspect and clean the air conditioner/heat pump filters immediately to remove any imminent hazard. Continue to clean these filters every 30 days in accordance with manufacturer's recommendations, which can be found at www.regcen.com/PTAC.
Product Images
Product Information
Full Description:
These PTACs are owned mainly by commercial and institutional organizations and are used in the lodging industry, apartments, hospitals, nursing homes and assisted living facilities, schools, and government buildings. A small number of the recalled units are owned by individual homeowners. The PTACs are beige in color and are intended for through-the-wall installation. Goodman manufactured all of the recalled units, which were sold under the Amana, Trane, and American Standard brand names. Goodman and Trane/American Standard are separate, unrelated entities. The recalled PTACs consist of Amana brand units manufactured from January 1996 through March 2003, and Trane and American Standard brand units manufactured from January 1996 through August 2002, that use electric heaters rated at 3.5 kilowatts (kW) or greater. Brand Name Serial and Model Numbers Amana Serial numbers begin with 96, 97, 98, 99, 00, 01, 02, 0301, 0302, or 0303 Model numbers begin with:PTH073A35; PTH074A35; PTH093A35; PTH093A50; PTH094A35; PTH094A50; PTH123A35; PTH123A50; PTH124A35; PTH124A50; PTH153A35; PTH153A50; PTH154A35; PTH154A50; PTC073A35; PTC074A35; PTC093A35; PTC093A50; PTC094A35; PTC094A50; PTC123A35; PTC123A50; PTC124A35; PTC124A50; PTC153A35; PTC153A50; PTC154A35; PTC154A50 Trane and American Standard Serial numbers begin with A96, A97, A98, A99, A00, A01, A02 Model numbers begin with:PTHC0701G; PTHC0702G; PTHC0901G; PTHC0901J; PTHC0902G; PTHC0902J; PTHC1201G; PTHC1201J; PTHC1202G; PTHC1202J; PTHC1501G; PTHC1501J; PTHC1502G; PTHC1502J; PTEC0701G; PTEC0702G; PTEC0901G; PTEC0901J; PTEC0902G; PTEC0902J; PTEC1201G; PTEC1201J; PTEC1202G; PTEC1202J; PTEC1501G; PTEC1501J; PTEC1502G; PTEC1502J The serial and model numbers are below the operating controls under the front cover assembly. To check the serial and model numbers, remove the front cover by pulling it from the bottom straight out until the clips release, then lifting it up. For some units, it is first necessary to remove two ΒΌ" screws (in the filter compartment) that secure the front cover.
Product Codes/Lot Numbers:
(About 875,000)
Official Source
Always verify recall information with the official CPSC source:
View on CPSC.govCPSC Recall Number: 04229
Related Recalls
Packaged Terminal Air Conditioners/Heat Pumps (PTACs)
Goodman Company, L.P. of Houston, Texas
The outdoor fan motors can overheat, posing burn and fire hazards.
Packaged Terminal Air Conditioner/Heat Pumps (PTAC) and Room Air Conditioners (RAC)
Goodman Company, L.P. of Houston, Texas
The power cords on the air conditioning and heating units can overheat, posing burn and fire hazards.
Amana, Century, Comfort-Aire, Goodman and York International Packaged Terminal Air Conditioner/Heat Pump ("PTAC") units
Goodman Company, L.P. of Houston, Texas
The power cords on the air conditioning and heating units can overheat, posing burn and fire hazards.