Siebe actuators

Class I - Dangerous

What Should You Do?

  1. Check if you have this product:
    (Up to 560,000)
  2. Do not eat it: Even if it looks and smells fine, do not consume this product.
  3. Throw it away or return it: You can return the product to the store for a full refund.
  4. Seek medical attention if needed: If you've consumed this product and feel unwell, contact your doctor immediately.
  5. Report problems: Report any issues to the FDA's Safety Reporting Portal.

⚠️ Emergency: If you experience severe symptoms after consuming this product, call 911 or Poison Control at 1-800-222-1222.

Recall Details

Company:
Unknown Manufacturer
Reason for Recall:
A spring mechanism integrated with the damper is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.
Classification:
Class I - Dangerous

Dangerous or defective products that predictably could cause serious health problems or death.

Status:
ongoing
Hazard:
A spring mechanism integrated with the damper is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.
Remedy:
To be eligible for a free actuator replacement, the building owner must test the actuator and report the results to Invensys. Only actuators that fail testing will be replaced.

Product Information

Full Description:

These MA-200 and MA-200-1 series actuators were used in fire and smoke dampers that were manufactured by various companies from December 1993 through October 1999, which were installed by private contractors in commercial and residential buildings. The actuators have manufacture date codes of 9348 through 9947. See the associated recall alert for more details on the dampers and companies involved.

Product Codes/Lot Numbers:

(Up to 560,000)

Official Source

Always verify recall information with the official CPSC source:

View on CPSC.gov

CPSC Recall Number: 03003

Related Recalls

AMP MP2 Smart Fitness Machine

Unknown Manufacturer

Class I - Dangerous

The arm on the MP2 model of the fitness machine does not lock properly, which can allow the arm to swing unexpectedly, posing a risk of laceration or serious injury.

Dec 18, 2025 Furniture Nationwide View Details →
Class I - Dangerous

The power strips do not contain supplementary overcurrent protection, which creates a risk of fire if the power strips are overloaded. The resulting fire can cause serious injury or death from smoke inhalation and burns.

Dec 18, 2025 Electronics Nationwide View Details →